Bolt torque calculator.
Pick a thread, a grade, a nut factor and a target preload, and get the clamp force and the tightening torque, with the working shown. Strengths come from our grade pages; the formulas are the standard ones, written out below.
Tensile stress area: As = 0.7854 × (D − 0.9743 / n)² = 0.6057 sq in.
ASTM A193 B7, 2½ and under: minimum yield strength 105 ksi (105,000 psi) (grade data)
Preload: F = 75% × 105,000 psi × 0.6057 sq in. = 47,699 lbf
Torque: T = K × D × F = 0.20 × 1 in.× 47,699 lbf ÷ 12 = 795 ft·lbf
An estimate, not a specification. K varies with finish, coating, lubricant, washers and tightening method, so the same torque can give very different preloads. Verify against your joint design, the gasket or equipment maker's figures, or a test on the actual parts.
Preload first, then torque.
A bolt holds a joint by being stretched, and the clamp force that stretch creates is the preload. The calculator works out the preload you asked for, then the torque that should produce it.
Metric (ISO 898-1): As = 0.7854 × (d − 0.9382 P)², with d the nominal diameter and P the pitch, in mm.
Typical K values.
K changes the answer more than anything else. These are typical, approximate starting points, not guarantees; use the value your lubricant maker publishes, or measure it.
Example torque charts.
The same calculation run for every size of two common grades, at 75 percent of minimum yield. Change the grade, K or target in the calculator above for your own case. Coated or lubricated bolts need the K for that condition.
| Thread | As (sq in.) | Yield, min | Preload at 75% (lbf) | Torque, K = 0.20 | Torque, K = 0.15 | ||
|---|---|---|---|---|---|---|---|
| ft·lbf | N·m | ft·lbf | N·m | ||||
| 1/4"-20 UNC | 0.0318 | 105 ksi | 2,504 | 10.4 | 14.1 | 7.83 | 10.6 |
| 5/16"-18 UNC | 0.0524 | 105 ksi | 4,127 | 21.5 | 29.1 | 16.1 | 21.9 |
| 3/8"-16 UNC | 0.0775 | 105 ksi | 6,103 | 38.1 | 51.7 | 28.6 | 38.8 |
| 7/16"-14 UNC | 0.1063 | 105 ksi | 8,371 | 61.0 | 82.8 | 45.8 | 62.1 |
| 1/2"-13 UNC | 0.1419 | 105 ksi | 11,175 | 93.1 | 126 | 69.8 | 94.7 |
| 9/16"-12 UNC | 0.1819 | 105 ksi | 14,325 | 134 | 182 | 101 | 137 |
| 5/8"-11 UNC | 0.2260 | 105 ksi | 17,798 | 185 | 251 | 139 | 189 |
| 3/4"-10 UNC | 0.3345 | 105 ksi | 26,342 | 329 | 446 | 247 | 335 |
| 7/8"-9 UNC | 0.4617 | 105 ksi | 36,359 | 530 | 719 | 398 | 539 |
| 1"-8 UNC | 0.6057 | 105 ksi | 47,699 | 795 | 1,078 | 596 | 808 |
| 1-1/8"-7 UNC | 0.7633 | 105 ksi | 60,110 | 1,127 | 1,528 | 845 | 1,146 |
| 1-1/4"-7 UNC | 0.9691 | 105 ksi | 76,317 | 1,590 | 2,156 | 1,192 | 1,617 |
| 1-3/8"-6 UNC | 1.1549 | 105 ksi | 90,948 | 2,084 | 2,826 | 1,563 | 2,119 |
| 1-1/2"-6 UNC | 1.4053 | 105 ksi | 110,667 | 2,767 | 3,751 | 2,075 | 2,813 |
| 1-3/4"-5 UNC | 1.8995 | 105 ksi | 149,586 | 4,363 | 5,915 | 3,272 | 4,436 |
| 2"-4.5 UNC | 2.4982 | 105 ksi | 196,733 | 6,558 | 8,891 | 4,918 | 6,668 |
| 2-1/4"-4.5 UNC | 3.2477 | 105 ksi | 255,756 | 9,591 | 13,003 | 7,193 | 9,753 |
| 2-1/2"-4 UNC | 3.9988 | 105 ksi | 314,906 | 13,121 | 17,790 | 9,841 | 13,342 |
| 2-3/4"-4 UNC | 4.9340 | 95 ksi | 351,548 | 16,113 | 21,846 | 12,084 | 16,384 |
| 3"-4 UNC | 5.9674 | 95 ksi | 425,177 | 21,259 | 28,823 | 15,944 | 21,617 |
| 3-1/4"-4 UNC | 7.0989 | 95 ksi | 505,797 | 27,397 | 37,146 | 20,548 | 27,859 |
| 3-1/2"-4 UNC | 8.3286 | 95 ksi | 593,413 | 34,616 | 46,933 | 25,962 | 35,199 |
| 3-3/4"-4 UNC | 9.6565 | 95 ksi | 688,026 | 43,002 | 58,302 | 32,251 | 43,727 |
| 4"-4 UNC | 11.0826 | 95 ksi | 789,635 | 52,642 | 71,373 | 39,482 | 53,530 |
Calculated with this page's formulas: B7 minimum yield 105 ksi to 2-1/2 in. and 95 ksi over 2-1/2 to 4 in. (ASTM A193). Estimates only; K = 0.20 is a typical dry-steel value and 0.15 a typical lubricated value. Use the K for your finish and lubricant.
| Thread | As (mm²) | Yield, min | Preload at 75% (kN) | Torque, K = 0.20 | Torque, K = 0.15 | ||
|---|---|---|---|---|---|---|---|
| N·m | ft·lbf | N·m | ft·lbf | ||||
| M5 × 0.8 | 14.2 | 940 MPa | 10.0 | 10.0 | 7.38 | 7.51 | 5.54 |
| M6 × 1 | 20.1 | 940 MPa | 14.2 | 17.0 | 12.5 | 12.8 | 9.41 |
| M8 × 1.25 | 36.6 | 940 MPa | 25.8 | 41.3 | 30.5 | 31.0 | 22.8 |
| M10 × 1.5 | 58.0 | 940 MPa | 40.9 | 81.8 | 60.3 | 61.3 | 45.2 |
| M12 × 1.75 | 84.3 | 940 MPa | 59.4 | 143 | 105 | 107 | 78.9 |
| M14 × 2 | 115.4 | 940 MPa | 81.4 | 228 | 168 | 171 | 126 |
| M16 × 2 | 156.7 | 940 MPa | 110 | 354 | 261 | 265 | 196 |
| M18 × 2.5 | 192.5 | 940 MPa | 136 | 489 | 360 | 366 | 270 |
| M20 × 2.5 | 244.8 | 940 MPa | 173 | 690 | 509 | 518 | 382 |
| M22 × 2.5 | 303.4 | 940 MPa | 214 | 941 | 694 | 706 | 521 |
| M24 × 3 | 352.5 | 940 MPa | 249 | 1,193 | 880 | 895 | 660 |
| M27 × 3 | 459.4 | 940 MPa | 324 | 1,749 | 1,290 | 1,312 | 967 |
| M30 × 3.5 | 560.6 | 940 MPa | 395 | 2,371 | 1,749 | 1,779 | 1,312 |
| M33 × 3.5 | 693.6 | 940 MPa | 489 | 3,227 | 2,380 | 2,420 | 1,785 |
| M36 × 4 | 816.7 | 940 MPa | 576 | 4,146 | 3,058 | 3,109 | 2,293 |
| M39 × 4 | 975.8 | 940 MPa | 688 | 5,366 | 3,958 | 4,024 | 2,968 |
| M42 × 4.5 | 1120.9 | 940 MPa | 790 | 6,638 | 4,896 | 4,978 | 3,672 |
| M45 × 4.5 | 1306.0 | 940 MPa | 921 | 8,287 | 6,112 | 6,215 | 4,584 |
| M48 × 5 | 1473.2 | 940 MPa | 1,039 | 9,971 | 7,354 | 7,478 | 5,515 |
| M52 × 5 | 1757.8 | 940 MPa | 1,239 | 12,888 | 9,506 | 9,666 | 7,129 |
| M56 × 5.5 | 2030.0 | 940 MPa | 1,431 | 16,029 | 11,822 | 12,022 | 8,867 |
| M60 × 5.5 | 2362.0 | 940 MPa | 1,665 | 19,983 | 14,738 | 14,987 | 11,054 |
| M64 × 6 | 2676.0 | 940 MPa | 1,887 | 24,148 | 17,811 | 18,111 | 13,358 |
Calculated with this page's formulas: class 10.9 minimum yield 940 MPa (ISO 898-1 / ASTM F568M). Estimates only; use the K for your finish and lubricant.
Bolt torque: common questions.
How do you calculate bolt torque?
With the short-form torque equation T = K × D × F: T is the tightening torque, K the nut factor, D the nominal bolt diameter and F the preload (clamp force) you want. Pick the preload first, usually as a percentage of the bolt's minimum yield or proof strength times its tensile stress area, then multiply by K and D. In inch units divide by 12 to get ft·lbf; in metric, with d in mm and F in newtons, divide by 1000 to get N·m.
What is the nut factor K?
K is an experimental factor that lumps together thread friction, friction under the nut or head, and the thread geometry. It is not a pure friction coefficient. Dry, as-received steel is often taken as about 0.20; lubricants bring it down, typically to somewhere around 0.10 to 0.18 depending on the product. The best value is the one your lubricant maker publishes or one measured on the actual parts.
What preload should I tighten a bolt to?
That is set by the joint design. Many bolted joints target roughly 50 to 75 percent of the bolt's minimum yield strength; flanged joints follow the bolt stress set by the designer, the gasket maker or a standard such as ASME PCC-1. This calculator defaults to 75 percent of minimum yield and lets you change it.
Why does lubrication change the torque so much?
Most of the torque you apply goes into overcoming friction, so only a small part stretches the bolt. Lower friction means more of the same torque becomes preload. Using a dry-steel torque on a lubricated bolt can overload it, which is why the K you use must match the actual finish and lubricant.
Does this work for stud bolts with two nuts?
Yes. Use the stud's nominal diameter and thread and the K for the nut face and threads you will tighten. The torque is applied at the nut.
Why is a grade marked 'not listed for this size'?
Strength requirements change with diameter and some grades only cover certain sizes. The calculator uses only the size ranges printed on our grade pages, so a size outside them is not given a number. For example, our data for property class 8.8 covers M20 and up.
How accurate is a torque calculation?
It is an estimate. Friction varies from part to part and with coatings, lubricants, washers and tightening speed, so preload achieved by torque alone can easily vary by 25 percent or more. Where preload is critical, use tensioning, direct tension indicators, ultrasonic measurement or a torque-tension test on the actual parts.
Estimates only, with no guarantee. The nut factor varies with finish, coating, lubricant, washers and tightening method; verify any torque against your joint design, the equipment or gasket maker's instructions, or a test on the actual parts. Strength values are specification minimums from our grade pages; thread sizes and stress areas follow ASME B1.1 and ISO 898-1.
Engineering tools from our shop.
Bolt size chart
Hex and heavy hex bolt and cap screw head dimensions: across flats, across corners, head height. ASME B18.2.1 and ISO 4014.
Heavy hex nut chart
Heavy hex, hex and jam nut dimensions: width across flats and corners, thickness. ASME B18.2.2 and ISO 4032.
Wrench size chart
The wrench or socket for every hex and heavy hex bolt and nut, 1/4 to 4 in. and M5 to M64, inch and DIN/ISO.